Stranded capacity
A specific IT device requires sufficient capacity of all of the five above elements. Yet these elements are almost never available in an exact balance of capacity to match a specific IT load. Invariably, there are locations with rack space but without available cooling, or spaces with available power but with no available rack space. Capacity of one type that cannot be used because one of the other four capacities listed above has been used to its maximum capacity is called stranded capacity. Stranded capacity is undesirable and can seriously limit the performance of a data center. Unfortunately, most data centers have significant stranded capacity issues, including the following common examples:
Depending on the situation and the architecture of the power and cooling system, it might be impossible to utilize stranded capacity or it might be that only minor investments are needed to free stranded capacity so that it can be effectively used. By definition, utilizing stranded capacity comes at a cost. It is often necessary to take down part of the installation or install new power and cooling components. |